Cooling Tower Water Treatment: Cycles, Scale and Blowdown

By SubcontractorHub Editorial Team·Published October 2026

Contractor reviewing a commercial water treatment scope at a desk

Short version: a cooling tower evaporates water and concentrates whatever was in the makeup. Cycles of concentration say how far you let that go. Blowdown is the water you dump to hold the cycles. Treatment is what lets you run those cycles without coating the fill in scale, eating the steel, or growing biofilm. Silica, hardness and biology set the ceiling. The arithmetic is in the blowdown calculator.

Commercial water treatment dealers meet cooling towers on office buildings, hospitals, campuses and plants that already buy softeners or reverse osmosis for other uses. The tower is a different machine. It is open to the air, it runs warm, and the bill for water and sewer is tied directly to how many cycles the chemistry will allow. This guide explains the water balance, the three failure modes, and where makeup pretreatment fits. Broader commercial applications are in the commercial water treatment guide.

What the Tower Does to Water

Condenser water circulates through the tower. A fraction of it evaporates, which is how the heat leaves. Evaporation is nearly pure water, so dissolved minerals stay behind and the basin gets saltier every hour the tower runs. A smaller fraction leaves as drift, droplets blown out of the fan. The rest is blowdown, water bled to drain on purpose so the concentration stops rising.

Makeup is whatever you add to replace all three. If you bleed very little, you save water and you scale the tower. If you bleed constantly, the surfaces stay cleaner and the water bill climbs. Treatment exists to move that trade in the building's favor without pretending chemistry can replace a water balance.

Cycles of Concentration

Cycles are a ratio. Measure conductivity in the tower and conductivity in the makeup. Divide. Three cycles means the tower water holds about three times the dissolved solids of the city water feeding it. Some programs calculate cycles from a single ion, such as chloride, that does not drop out as scale. Conductivity is the everyday meter reading, and it is good enough to run the building if you also have a periodic lab sheet.

There is no universal “best” cycle count. Soft, low-silica makeup can run higher cycles than hard, high-silica makeup. A target copied from another city is how fill gets cemented into the tower. Start from the makeup analysis. The ions that hit a limit first, often calcium hardness, alkalinity, phosphate or silica, set the maximum cycles. Everything else in the program is there to push that limit a bit higher or to protect metal while you sit under it.

Blowdown, Evaporation and Makeup

The planning equations used on this site's calculator are straightforward. Recirculation is either measured in gallons per minute or estimated at about 3 gpm per ton of chiller capacity. Evaporation in gpm is an evaporation factor times recirculation times the temperature drop in degrees Fahrenheit. The default factor is 0.0008 per degree, a stand-in for most of the heat leaving as evaporation. Hot, dry climates can sit closer to 0.001.

Blowdown is then about evaporation divided by (cycles minus one), minus drift, because drift has already thrown some concentrated water away. Makeup is evaporation plus blowdown plus drift. Raise the cycles and blowdown falls. The water and sewer savings are real, and they stop being real the moment silica or hardness scale forces you back down.

Drift on a modern tower with eliminators is a small percentage of recirculation. Older towers drift more. Drift is also the path aerosols take off the site, which is why biology is not only a slime problem inside the fill. Run your own tons, range and cycles through the cooling tower blowdown calculator before you promise a water-savings number on a proposal.

Scale, Corrosion and Biofouling

These three fight each other. A program that drives pH up to hold corrosion down can precipitate calcium carbonate. A program that holds pH down to stop scale can rust steel. Biofilm hides under both and insulates heat-exchange surface so the chiller works harder. You treat all three, or the one you ignored becomes the callback.

ProblemWhat you seeWhat drives it
ScaleWhite or gray crust on fill, nozzles and heat-exchange surfaces. Approach temperature worsens.Calcium carbonate, calcium phosphate, silica. Higher cycles and higher pH push precipitation.
CorrosionRust, pitting, thinned steel, or white rust on galvanized towers.Low pH, high conductivity, dissolved oxygen, dissimilar metals, and a program that chased scale so hard it left the metal bare.
BiofoulingSlime on fill, foul odor, rising bacteria counts, clogged strainers.Warm water, sunlight, nutrients from makeup or process contamination, and a biocide program that is not documented.
Fouling from dirtMud in the basin, plugged nozzles, cloudy water after a storm.Airborne dust, nearby construction, and a basin that is never cleaned. Chemistry will not replace a shovel.

Inhibitors, acid or alkali feed, and biocides are specified from the water and from the metals in the tower and the condenser. This page is not a chemical recipe. The dealer's job on the first visit is to identify which of the four rows is already happening, not to drop a drum of “tower chemical” and leave.

Silica and Other Limits

Silica scale is stubborn. Once it plates onto fill or a heat exchanger, mechanical cleaning is miserable and acid cleaning is not a casual service call. Field programs often hold recirculating silica near or below about 150 ppm as SiO2 unless the inhibitor supplier has documented a different ceiling for that chemistry. That 150 ppm figure is the planning default in the blowdown calculator. It is a ceiling to check, not a law.

Maximum cycles from silica alone are the ceiling divided by silica in the makeup. Makeup at 30 ppm silica and a 150 ppm ceiling allows about 5 cycles before silica, by itself, says stop. Calcium hardness or alkalinity may say stop sooner. If the building needs more cycles than the makeup allows, the makeup has to change. That is pretreatment: a softener on hardness, or reverse osmosis or deionization when silica or TDS is the wall. The deionized water system calculator is the sizing companion when the spec really is DI, which is a narrower case than “the tower is scaling.”

Makeup Water

Get a current analysis of whatever feeds the tower. City water changes by season. A well, a reclaim line or a blend of condensate and city water changes the whole program. Hardness, alkalinity, silica, pH, conductivity and a note about phosphate or other corrosion inhibitor already in the city water are the minimum. Without that sheet, a cycles target is a guess.

Softening makeup removes calcium and magnesium so calcium carbonate is less likely to set the cycle limit. It does not remove silica. It adds sodium. It can be the right project when the water bill is the customer's complaint and hardness is the ion in the way. It is the wrong project when the basin is full of mud and nobody has cleaned it. Commercial softener sizing, for this and for other process loads, belongs in the commercial guide and in a softener calculator fed by the actual gallons, not by a bathroom count.

Biology Is Part of the Program

Legionella associated with building water systems is why cooling towers are no longer a “keep the chiller happy” side task. ASHRAE Standard 188 is the published framework many facility programs use for risk management. A treatment contract that never mentions testing, biocide, or who is responsible for the basin cleaning is thin. So is a contract that quotes a kill claim without a sample plan.

Practically, the dealer logs conductivity, pH, inhibitor residual and a biological check on a schedule, and writes down blowdown setpoint changes. Drift eliminators have to be in place. Dead legs and idle towers in the shoulder season need a procedure, not a hope that the fan being off makes the basin safe. None of that requires an invented infection statistic to be worth putting in the scope.

What a Dealer Should Put on the Proposal

A useful cooling-tower scope has the makeup analysis, the current and target cycles, the blowdown and makeup the calculator produced, the limit that sets those cycles, the chemical or pretreatment that defends the limit, and the visit schedule. Water savings, if you state them, should be the calculator's output at the customer's rates, labeled as an estimate.

The same customer may already buy salt, filters or membranes for a kitchen, a lab or a boiler. Water treatment software is how those routes stay on one account instead of in a separate notebook for “the tower guy.” The tower is commercial work. Quote it like commercial work: with the numbers attached and a service cadence that survives the technician who sold it.

Frequently Asked Questions

What is cooling tower water treatment?

It is the program that keeps recirculating condenser water from scaling, corroding or growing biofilm as it concentrates. A tower evaporates pure water and leaves minerals behind. Treatment is the combination of controlled blowdown, the right cycles of concentration for the makeup water, and chemicals or pretreatment that hold scale, corrosion and biological growth inside limits the metallurgy can live with.

What are cycles of concentration?

Cycles of concentration compare dissolved solids in the tower water with dissolved solids in the makeup water. Conductivity is the field measurement people use. At 4 cycles, the tower water is about four times as concentrated as the makeup. Higher cycles mean less water sent to the sewer. They also mean scale and silica are closer to the point where they drop out. The limit is set by the makeup analysis, not by a single number that fits every city.

How is blowdown calculated?

Evaporation is set by the recirculation rate and the temperature drop across the tower. Blowdown is approximately evaporation divided by cycles minus one, with a small correction because drift also removes concentrated water. Makeup then equals evaporation plus blowdown plus drift. The cooling tower blowdown calculator on this site runs that water balance from tons or gallons per minute.

What is a silica limit on a cooling tower?

Silica in the recirculating water is a common scale limit because silica scale is hard to remove once it forms on fill and heat-exchange surfaces. A planning ceiling often used in the field is about 150 ppm as SiO2, which is the default on this site's blowdown calculator. It is not a code. The water treater may set a lower or higher ceiling from the rest of the chemistry and from the inhibitor program. Maximum cycles are then that ceiling divided by silica in the makeup.

Why do cooling towers grow bacteria?

Warm, aerated, nutrient-bearing water is a habitat. Drift can carry aerosols off the tower. Legionella is the organism that made cooling-tower biology a facilities issue, and ASHRAE Standard 188 is the risk-management framework many building programs follow. Biocide, cleanliness and documented testing are part of treatment. They are not optional add-ons once a tower serves an occupied building.

Does a softener or RO belong on cooling tower makeup?

Sometimes. Hard makeup water limits how many cycles you can run before calcium scale forms. Softening the makeup can raise allowable cycles and cut blowdown, which is a water bill conversation, not an automatic equipment sale. Reverse osmosis or deionization is for makeup that is already too high in silica or other ions for the cycles the plant needs. Size that equipment from the analysis. Do not put a residential softener on a tower and call it a program.

Related Guides & Tools

Quote the Tower With the Water Balance Attached

30-minute demo. See how dealers keep commercial water accounts, service visits and the makeup analysis on one record instead of a route sheet in the truck.

Book a Demo

SubcontractorHub

See How Top Contractors Close More Jobs

AI proposals, sales pipeline, and project management — all in one platform.

  • ✓AI-powered proposals in the field
  • ✓CRM built for contractor sales
  • ✓Project tracking from sale to install
Book a Free Demo →

30 minutes. No commitment.