Free HVAC Tool
HVAC Duct Sizing Chart & CFM Calculator
Enter room square footage (or CFM) to get the recommended round duct diameter, air velocity in FPM, and a noise rating. Supports supply branches, return ducts, and main trunks — with flex duct adjustment.
Built by SubcontractorHub — the software HVAC contractors use to quote, finance, and run every job.
Book a DemoCalculate the Right HVAC Duct Size
Enter room size or a known CFM requirement to get an instant round duct diameter recommendation with velocity and noise check.
Required CFM
200
Min. duct size
8" round
Air velocity
573 FPM
Velocity rating
Good
Round duct options
| Diameter | Max CFM | Velocity at 200 CFM | Noise rating |
|---|---|---|---|
| 8" round Recommended | 240 | 573 FPM | Good |
| 9" round | 320 | 453 FPM | Good |
| 10" round | 410 | 367 FPM | Low |
This is a simplified estimate. Proper duct sizing requires an ACCA Manual J load calculation and Manual D duct design by a licensed HVAC contractor or engineer. Duct length, fittings, static pressure, and system balancing all affect actual sizing requirements.
HVAC Duct Sizing Chart: CFM by Duct Size
Prefer to size ductwork off a chart instead of a calculator? These are the duct size and CFM figures HVAC contractors use for residential takeoffs — round and rectangular, rigid and flex. Every row is generated from the same capacity curve the calculator above uses, so the chart and the tool always agree. For the software side of the job, see our HVAC contractor platform and HVAC contractor software.
Round Duct Sizing Chart (CFM by Duct Size)
Rigid metal round duct capacity at a 0.1" w.g. per 100 ft friction rate. The flex column applies the standard 25% friction penalty — flex duct carries roughly 20% less air than rigid duct of the same diameter.
| Duct diameter | CFM range | Max CFM (rigid) | Max CFM (flex) | Velocity at max |
|---|---|---|---|---|
| 4" round | 25–50 CFM | 50 CFM | 40 CFM | 573 FPM |
| 5" round | 40–80 CFM | 80 CFM | 65 CFM | 587 FPM |
| 6" round | 60–120 CFM | 120 CFM | 95 CFM | 611 FPM |
| 7" round | 90–175 CFM | 175 CFM | 140 CFM | 655 FPM |
| 8" round | 120–240 CFM | 240 CFM | 190 CFM | 688 FPM |
| 9" round | 160–320 CFM | 320 CFM | 255 CFM | 724 FPM |
| 10" round | 205–410 CFM | 410 CFM | 330 CFM | 752 FPM |
| 12" round | 300–600 CFM | 600 CFM | 480 CFM | 764 FPM |
| 14" round | 415–830 CFM | 830 CFM | 665 CFM | 776 FPM |
| 16" round | 550–1100 CFM | 1100 CFM | 880 CFM | 788 FPM |
| 18" round | 700–1400 CFM | 1400 CFM | 1120 CFM | 792 FPM |
| 20" round | 875–1750 CFM | 1750 CFM | 1400 CFM | 802 FPM |
Rectangular Duct Size Chart (CFM by Duct Size)
Rectangular sheet-metal duct converted to its equivalent round diameter using the ASHRAE (Huebscher) equation, then rated against the same capacity curve as the round chart above.
| Rectangular size | Equivalent round | Max CFM |
|---|---|---|
| 8×6" | 7.6" round | 210 CFM |
| 10×6" | 8.4" round | 270 CFM |
| 12×6" | 9.1" round | 335 CFM |
| 14×6" | 9.8" round | 390 CFM |
| 10×8" | 9.8" round | 390 CFM |
| 12×8" | 10.7" round | 470 CFM |
| 14×8" | 11.5" round | 550 CFM |
| 16×8" | 12.2" round | 620 CFM |
| 20×8" | 13.5" round | 770 CFM |
| 12×12" | 13.1" round | 730 CFM |
| 16×12" | 15.1" round | 980 CFM |
| 20×12" | 16.8" round | 1220 CFM |
| 16×20" | 19.5" round | 1665 CFM |
| 20×20" | 21.9" round | 2075 CFM |
Flex Duct CFM Chart (Flexible Duct Sizing)
Flexible duct has roughly 25% more friction loss than smooth rigid metal of the same diameter, so a flex run carries about 20% less air. This flex duct CFM chart applies that penalty to the capacity curve above — use it whenever the branch is flex rather than hard pipe. Every figure assumes the flex duct is pulled tight; sagging or compressed flex loses far more than 20%.
| Flex duct size | Max CFM (flex) | Same size in rigid | Flex size to match that rigid CFM |
|---|---|---|---|
| 4" (4 inch) flex duct | 40 CFM | 50 CFM | 5" flex |
| 5" (5 inch) flex duct | 65 CFM | 80 CFM | 6" flex |
| 6" (6 inch) flex duct | 95 CFM | 120 CFM | 7" flex |
| 7" (7 inch) flex duct | 140 CFM | 175 CFM | 8" flex |
| 8" (8 inch) flex duct | 190 CFM | 240 CFM | 9" flex |
| 9" (9 inch) flex duct | 255 CFM | 320 CFM | 10" flex |
| 10" (10 inch) flex duct | 330 CFM | 410 CFM | 12" flex |
| 12" (12 inch) flex duct | 480 CFM | 600 CFM | 14" flex |
| 14" (14 inch) flex duct | 665 CFM | 830 CFM | 16" flex |
| 16" (16 inch) flex duct | 880 CFM | 1100 CFM | 18" flex |
| 18" (18 inch) flex duct | 1120 CFM | 1400 CFM | 20" flex |
| 20" (20 inch) flex duct | 1400 CFM | 1750 CFM | over 20″ |
How Many CFM for Each Round Duct Size?
The same capacity figures written out in plain language, for when you just need to know how many CFM a given duct size will handle. The first number is rigid metal pipe; the second is the same diameter run in flexible duct.
Duct CFM Calculation Formula
Every figure in these charts comes from two pieces of arithmetic. If you would rather calculate duct CFM by hand than read it off a chart, this is the formula:
Round duct area (sq ft) = π × (diameter in inches ÷ 24)²
CFM = air velocity (FPM) × duct area (sq ft)
Equivalent round for rectangular duct = 1.30 × (a × b)0.625 ÷ (a + b)0.25
Worked example — an 8 inch round duct at 700 FPM: area = π × (8 ÷ 24)² = π × 0.1111 = 0.349 sq ft. Then CFM = 700 × 0.349 = 244 CFM, which is why the chart rates 8 inch pipe at roughly 240 CFM. Dividing the diameter by 24 rather than 12 converts it to a radius in feet in a single step.
To run the duct CFM calculation formula backwards — sizing ductwork from a known airflow instead of rating ductwork you already have — solve for area first: area = CFM ÷ FPM, then diameter = 24 × √(area ÷ π). For 400 CFM at 700 FPM that is 0.571 sq ft, which works out to a 10.2 inch duct, so you would install 10 inch rigid pipe or 12 inch flex.
Use this chart for quick field sizing and takeoffs. Final duct design should come from an ACCA Manual J load calculation and a Manual D duct design by a licensed HVAC contractor — total run length, fittings, and equipment static pressure all shift the real numbers.
How HVAC Duct Sizing Works
Start with the airflow requirement (CFM)
Every room or zone needs a specific amount of conditioned air. A rough residential rule of thumb is 1 CFM per square foot of floor area for cooling in a moderate climate, adjusted for ceiling height and climate severity. The more rigorous approach is a Manual J load calculation that accounts for insulation, window area, orientation, and local climate.
Select a duct size that handles the CFM at good velocity
Each duct size has a range of CFM it can carry while keeping air velocity in the comfortable zone (400–700 FPM for supply branches). Too small → high velocity, noisy airflow, and higher static pressure drop. Too large → low velocity, poor throw at registers, and potential stratification.
Adjust for flex duct friction
Flexible duct has approximately 25% more friction than smooth rigid metal duct at the same airflow. If you're using flex duct, size up one diameter compared to the rigid duct equivalent. Also keep flex duct stretched tight — kinked or compressed flex duct dramatically increases friction loss.
Verify with a full Manual D calculation
This calculator gives a starting point, not a final design. A complete ACCA Manual D calculation accounts for total duct length, number of elbows and fittings, system total external static pressure, and balancing across all branches. Always have a licensed HVAC contractor perform a Manual D design for new installations.
Common HVAC Duct Sizing Mistakes
Undersized main trunk
The main supply trunk must carry the total system airflow before it branches out. An undersized trunk causes high static pressure, forcing the blower to work harder, reducing efficiency, and shortening equipment life.
Using flex duct with same size as rigid
Flex duct requires a one-size-larger diameter compared to rigid metal for the same airflow. Using identical sizes for both materials results in an undersized flex run with noisy, high-velocity airflow.
Too many registers on one branch
Splitting one branch run to serve too many registers divides airflow too thin, leaving far rooms cold in summer. Each branch should be sized for its own load, not overloaded with additional tees downstream.
Ignoring return air capacity
An undersized return duct creates negative pressure in the living space, pulling unconditioned air through gaps and reducing system efficiency. Returns should be sized generously — at least equal in total area to the supply system.
Sharp bends in flex duct
A 90-degree bend in flexible duct can reduce effective diameter by 40% and increase friction by 50% or more. Route flex duct in gentle curves whenever possible. Sharp bends are one of the most common causes of poor airflow in residential retrofits.
Not accounting for equipment static pressure
Every air handler has a maximum external static pressure (ESP) it can operate against. Undersized ductwork raises static pressure, forcing the system into an operating range where airflow drops and efficiency falls. Match duct system design to the equipment's rated ESP.
From Load Numbers to a Signed Proposal
SubcontractorHub helps HVAC contractors build professional proposals, present good-better-best equipment tiers, and close jobs with financing and e-signature on the spot.
See How It WorksHVAC proposals built in minutes
Good-better-best equipment tiers
Energy savings shown per tier
Financing at the kitchen table
Digital signature and same-day close
HVAC Duct Sizing FAQ
How do I calculate duct size?
Calculate required CFM first (roughly 1 CFM per sq ft for moderate climates). Then select a round duct size where the air velocity falls in the comfortable range: 400–700 FPM for supply branches, 400–800 FPM for returns, 700–900 FPM for main trunks.
What size duct do I need for a 12×12 room?
A 144 sq ft room needs roughly 100–150 CFM. A 7-inch round duct (rated for 90–175 CFM) or a 6×8-inch rectangular equivalent is typical. In hot climates or rooms with large west-facing windows, size up to 8 inches.
What is CFM in HVAC?
CFM (Cubic Feet per Minute) is the volume of air a duct or system moves per minute. Residential systems typically move 350–450 CFM per ton of cooling. A 3-ton system moves about 1,200 CFM total, distributed across all supply registers.
What is the correct air velocity for HVAC ducts?
Supply branch ducts: 400–700 FPM. Return ducts: 400–800 FPM. Main supply trunks: 700–900 FPM. Above 900–1,000 FPM, ductwork generates noticeable noise. Below 400 FPM, air may not reach registers with adequate pressure.
What is Manual D duct sizing?
ACCA Manual D is the industry standard for residential duct system design. It calculates duct sizes based on friction rate, equivalent duct lengths, and airflow from a Manual J load calculation. Most codes now require Manual D for new construction.
How many CFM per ton of AC?
Residential systems are designed for 350–450 CFM per ton, with 400 CFM/ton being most common. A 3-ton system moves about 1,200 CFM. Under-ducted systems can't move enough air, causing the coil to freeze and reducing efficiency.
What is the difference between supply and return ducts?
Supply ducts carry conditioned air from the air handler to rooms. Return ducts carry room air back to be reconditioned. Returns are typically fewer, larger ducts; supplies are more numerous, smaller branches. A balanced system has approximately equal supply and return capacity.
Can I use flex duct instead of rigid?
Yes, but flex duct has 25% more friction than rigid metal. Size flex duct one diameter larger than the equivalent rigid duct recommendation. Keep flex duct stretched tight and avoid sharp bends — kinked flex duct dramatically reduces airflow.
How many CFM can an 8 inch round duct handle?
About 240 CFM as rigid metal pipe, with a comfortable working range of 120–240 CFM. The same 8 inch diameter in flex duct carries roughly 190 CFM. For comparison: 6 inch is 120 CFM rigid / 95 CFM flex, 10 inch is 410 / 330, and 12 inch is 600 / 480.
What is the formula to calculate duct CFM?
CFM = air velocity (FPM) × duct area (sq ft), where round duct area = π × (diameter ÷ 24)². An 8 inch duct at 700 FPM gives 0.349 sq ft × 700 = 244 CFM. Reverse it to size ductwork from airflow: area = CFM ÷ FPM, then diameter = 24 × √(area ÷ π).
HVAC Contractors: Close More Jobs With Better Proposals
SubcontractorHub gives HVAC contractors the tools to build professional proposals, present financing, and collect signatures on the spot.
Book a Free DemoResources
Related Guides & Tools
- Static Pressure Calculator (TESP & Friction Rate)
- HVAC CFM Calculator — Required Airflow
- HVAC Sizing Calculator (BTU/Tons)
- HVAC Replacement Cost Calculator
- HVAC SEER Savings Calculator
- Mini Split Sizing Calculator (Ductless)
- HVAC Contractor Software
- Best HVAC Software Guide
- How to Price Ductwork Jobs
- More Free Contractor Tools
This calculator provides simplified estimates. Proper duct sizing requires an ACCA Manual J and Manual D calculation by a licensed HVAC contractor.
All calculations are estimates based on historical information and should be verified by the user. This tool is provided as a free service for planning purposes only and is not a substitute for a professional assessment, a supplier quote, or applicable local code requirements.