Water Heater Expansion Tank: What Amtrol's ST-5 Prints

By SubcontractorHub Editorial Team·Published November 2026

Contractor reviewing a water heater expansion tank specification before a potable heater job

A water heater expansion tank on Amtrol's Therm-X-Trol card MC8520, marked 09/25 and fetched 23 November 2026, is not the gallon number painted on the heater. The ST-5 row prints a 2.0 gallon tank volume and a 0.9 gallon maximum acceptance volume. Acceptance is the water the tank can take. The shell is larger than that.

The same card sets factory precharge at 50 psig for the ST-5 and the ST-12, and at 40 psig from the ST-25V through the ST-210V. Maximum operating temperature from the ST-5 through the ST-210V is 200°F. Maximum working pressure is 150 psig. Sizing on the card is based on 40°F incoming water, a 150 psi temperature-and-pressure relief valve, and precharge equal to static supply pressure for the ST-5 and above.

What the Water Heater Expansion Tank Card Actually Lists

Two in-line rows extracted cleanly. The ST-1 row on the same table did not, so its diameter and height are not repeated here. The card does say the ST-1 is the model for tankless and point-of-use heaters up to 2 gallons, and that its factory precharge is a permanent air cell rather than the 50 psig charge used on the ST-5.

LineST-5ST-12
Tank volume2.0 gal4.4 gal
Max. acceptance0.9 gal3.2 gal
Diameter8 in11 in
Height13 in15 in
Connection3/4 NPTM3/4 NPTM
Shipping weight5 lb9 lb
Factory precharge50 psig50 psig

Divide the two ST-5 volumes and the ratio is 0.45. That is arithmetic from 0.9 and 2.0, not a second rating printed as a factor on this card. The ST-12 ratio from the same two columns is 3.2 divided by 4.4. Use the gallons the card prints when you order. Do not order from the ratio.

The card's quick-sizing charts sit under three maximum temperature settings. In the text of the PDF those charts did not stay in separate columns, so this page does not say which model the card assigns to a 40 gallon heater at a given pressure. Open the card for the cell. Quoting a mashed cell would invent a model.

Set the Water Heater Expansion Tank to the Supply, Not to the Sticker

Fifty psig is what the factory put in the ST-5. The sizing sentence says precharge should equal static supply pressure. If the street pressure is not 50, the tank still has to be set before it is full of water. A gauge on the drain, with the tank isolated, is the check. This page does not print a city's pressure.

The 200°F operating limit and the 150 psig working limit are the card's ceiling, not a target setpoint for the heater. The sizing basis also names a 150 psi temperature-and-pressure relief valve and 40°F incoming water. Those are the conditions under the charts. They are not a permit rule copied from a code book. No plumbing code page was fetched for this URL, so this article does not say a jurisdiction requires the tank.

Heater size itself is a different calculator. The water heater sizing calculator is the storage or recovery question. Replacement scope, without a model picked from this card, is the water heater replacement cost calculator. Pipe volume for a hydronic loop is the pipe volume calculator, and it is not this potable thermal tank.

Three Tanks People Mix Up With a Water Heater Expansion Tank

A well pressure tank holds drawdown for a pump. Troubleshooting that tank is a different article, pressure tank troubleshooting, and its air charge is not the 50 psig factory number on the ST-5. Do not set a well tank from this card.

A reverse osmosis storage tank holds product water. The reverse osmosis storage tank page quotes empty-tank air charges from Pentair manuals. Those psi figures are not an ST-5 precharge, and the gallons on that page are not acceptance volume for a heater.

Tankless heaters are called out on this card only as the ST-1 case, up to 2 gallons, with a permanent air cell. Flushing a tankless heat exchanger is the tankless water heater maintenance note from a Rinnai manual. Scale in the heat exchanger is not the expanded water this tank accepts.

Acceptance Volume Is the Number the Heater Cares About

A water heater expansion tank fails the job when someone orders the shell gallons and ignores acceptance. On the ST-5 the shell is 2.0 gallons and the tank can take 0.9. The other 1.1 gallons are not spare capacity for hot water. They are the air side that lets the 0.9 exist. Treating 2.0 as the amount of expansion the tank will swallow oversizes the story and undersizes the heater that needed the 0.9.

The ST-12 makes the same point with different gallons: 4.4 in the shell, 3.2 accepted. The air side is smaller as a share of the shell than on the ST-5, which is why the ratio is not a constant you can reuse on the next model. The stand models on the card, from the ST-25V up, print their own acceptance and a 40 psig factory charge. Copy the row you are buying. Do not scale the ST-5 by heater gallons in your head.

What the technician writes down is short. Static pressure measured. Precharge set to that pressure, tank empty. Model, including the acceptance gallons from the row. Heater volume and the temperature the card's chart was read at, read from the card, not from this article. Connection checked as 3/4 inch male on the two rows above. That note is the job record. A price is not on the card, so it is not on the note from this page.

The connection size is part of the order, not a footnote. Both rows that extracted cleanly are 3/4 inch male pipe thread. A 1/2 inch nipple is a different fitting, and this card does not list a 1/2 inch ST-5. Height is 13 inches on the ST-5 and 15 inches on the ST-12. That is the dimension on the card, not a clearance measured on a job. Shipping weight, 5 pounds and 9 pounds, is what the carton says. It is not a measure of how much water the diaphragm will accept.

Relief-valve discharge is the symptom people call about. The card's sizing basis names a 150 psi temperature-and-pressure valve as an assumption under the charts. It does not say the tank replaces that valve, and it does not say every discharge is an undersized tank. A valve that opens because the setpoint or the supply pressure is outside the chart is a different diagnosis. This URL stops at the specification table.

How a Contractor Uses the Card

  1. Read static supply pressure at the house. That number is the precharge target on this card for an ST-5 and larger.
  2. Confirm the tank is empty of water before you change the air charge. The card's 50 psig is the factory charge, not a measurement of your job.
  3. Pick the model from the chart on MC8520 for the heater volume, the max temperature, and the supply pressure. Do not pick it from a sentence on this page.
  4. Order from tank volume and acceptance, not from shipping weight. Five pounds is the ST-5 on a pallet label, not a capacity.
  5. Keep the connection straight: both clean rows are 3/4 inch male pipe thread.
  6. Leave well tanks and RO tanks on their own pages. The air charge is not interchangeable.

Frequently Asked Questions

What does Amtrol print for an ST-5 water heater expansion tank?

On sizing card MC8520, dated September 2025 and fetched 23 November 2026, the ST-5 is a 2.0 gallon tank with 0.9 gallon maximum acceptance, an 8 inch diameter, a 13 inch height, a 3/4 inch male connection, and a 5 pound shipping weight. Factory precharge for the ST-5 and ST-12 is 50 psig.

Is the factory precharge the pressure you leave in the tank?

The same card says sizing is based on precharge equal to static supply pressure for the ST-5 and above. Fifty psig is the factory charge, not a reason to skip the gauge on the house.

Is a water heater expansion tank the same as a well pressure tank?

No. A well tank is the pump's drawdown tank. This card is a thermal expansion tank on a closed potable heater. The reverse osmosis storage tank is a third product, with its own empty-tank air charge on a different page.

Which chart cell should you copy?

None from this article. The card has quick-sizing charts at more than one maximum temperature. The text extract did not keep those charts in separate columns, so this page quotes the specification table and the sizing basis, not a cell.

Spec the Tank From the Card, Then Track the Job

The model, the precharge, and the heater size belong on the work order, not in a text thread after the truck leaves.