By SubcontractorHub Editorial Team·Published November 2026

Quick Answer
Refrigerant recordkeeping on the EPA page fetched 20 November 2026 splits in two. A technician on a 50-pound ozone-depleting appliance gives the owner the amount added and the leak records. Disposal records for appliances from 5 to 50 pounds also cover substitute refrigerants such as HFCs. This is not a charge chart.
Refrigerant recordkeeping fails when a job file says only "refrigerant added" and never names the rule. The EPA recordkeeping overview fetched the same day separates a 50-pound ozone-depleting service record from a disposal record on a smaller appliance. The second one names substitutes. The first one, on that page, does not.
The overview says EPA regulations at 40 CFR Part 82, Subpart F, under Section 608, include recordkeeping that depends on who you are. A technician keeps a copy of the proof of certification at the place of business. That card is not the same sheet as the pounds added on a rooftop unit. Certification names, and what the exam covers, stay on HVAC certification. Practice questions are the EPA 608 practice test.
Refrigerant recordkeeping is not a GWP table. The gas name on new equipment is a different article. A2L refrigerant is the class list. This page does not restate GWPs. It asks which appliance the record is for, and which sentence on the fetched pages applies to that appliance.
The technician paragraph says a person servicing an appliance that contains 50 or more pounds of ozone-depleting refrigerant must give the owner an invoice that indicates the amount of refrigerant added. The same paragraph says the technician also provides records of leak inspections and of tests performed to verify repairs of leaking appliances at that size. The owner paragraph says the owner keeps servicing records of the date and type of service and the quantity added, and keeps the leak-inspection and verification records.
40 CFR 82.157, fetched the same day, is the leak-repair section the overview is summarizing. It says that as of 10 April 2020 the section applies only to appliances with a full charge of 50 or more pounds of any class I or class II refrigerant, or a blend containing a class I or class II refrigerant. The next sentence says the requirements do not apply to appliances containing solely substitute refrigerants. A system charged only with a substitute is outside that section on the text that was fetched. This article does not fill that gap with a different rule that was not opened.
Where the section does apply, the leak rates it prints are 20 percent for commercial refrigeration equipment, 30 percent for industrial process refrigeration equipment, and 10 percent for comfort cooling appliances, or other appliances with a full charge of 50 or more pounds that the first two lines do not cover. Repair is within 30 days of the addition that exceeded the rate, or 120 days if an industrial process shutdown is required. An initial verification test and a follow-up test document the repair.
| Line | Who or what | What the fetched page prints |
|---|---|---|
| Who | Technician on a 50-pound ozone-depleting appliance | Invoice with the amount added, plus leak-inspection and verification records |
| Who | Owner or operator of that appliance | Date and type of service, quantity added, leak inspections, verification tests |
| Trigger | Leak rate in 82.157, class I or II only | 10 percent comfort cooling, 20 percent commercial refrigeration, 30 percent industrial process |
| Clock | Repair window in that section | 30 days, or 120 days if an industrial process shutdown is required |
| Report | 125 percent of the full charge in a calendar year | EPA overview: due 1 March for the prior year |
| Smaller appliance | Disposal of 5 to 50 pounds | EPA overview: ozone-depleting and substitute refrigerant, such as HFCs |
When someone other than the owner does the work, 82.157 says that person gives the owner the appliance, the date, the parts, the type of work, the name of the person, and the amount and type added or removed. Full charge and the leak-rate method stay on the owner's list. Leak inspections record the date, the methods, each leak found, and a certification that visible and accessible parts were inspected. Those records are kept at least three years. Full-charge information is kept until three years after retirement. A 125 percent leak in a calendar year is reported by 1 March. EPA prefers 608reports@epa.gov.
The same EPA overview says technicians disposing of appliances from 5 to 50 pounds must keep disposal records, typically field-installed splits, and that this requirement applies to ozone-depleting and substitute refrigerant, such as HFCs. The list is location and date of recovery, type recovered, monthly totals, and amounts sent for reclamation. The 10 percent comfort-cooling line was not written, on the fetched text, for an appliance that contains solely a substitute. Do not paste it onto that disposal record.
No page that extends these leak rates to HFCs under a later statute was fetched on 20 November 2026. If that extension exists, it is not quoted here. A shop whose fleet is only R-410A, R-32, or R-454B should not treat the 10, 20, and 30 percent lines as its leak law on the strength of this article. The disposal sentence that names HFCs is the one that was fetched for substitutes, and it is a disposal record, not a leak-rate table.
Cylinder layout is the HVAC van setup guide. Demand is the public result list. Ahrefs was not refreshed and has no volume row for this head term. No fine and no SubcontractorHub storage claim were added.
On the EPA overview fetched 20 November 2026, a technician who services an appliance with 50 or more pounds of ozone-depleting refrigerant gives the owner an invoice with the amount added, plus records of leak inspections and of tests that verify repairs. The same page says the owner keeps the service date, the type of service, and the quantity added.
Not on the rule text fetched the same day. 40 CFR 82.157 says that, as of 10 April 2020, the section applies to appliances with 50 or more pounds of a class I or class II refrigerant, or a blend that contains one, and that it does not apply to appliances containing solely substitute refrigerants. This page does not claim a later rule copied those leak rates onto HFCs.
The EPA overview says technicians disposing of appliances that contain between 5 and 50 pounds of refrigerant must keep disposal records, and that this requirement applies to ozone-depleting and substitute refrigerant, such as HFCs. The records it names are location and date of recovery, type recovered, monthly totals, and amounts sent for reclamation.
Section 82.157 says the records identified in its recordkeeping paragraph must be kept for at least three years in electronic or paper format, unless that paragraph says otherwise. Full-charge information is kept until three years after the appliance is retired. This page does not add a shop policy on top of that.